30/07/05 UW ARCHIVE 100.0 2005 W Anderson9BusTest Case BUS DATA FOLLOWS 9 ITEMS 1 Bus1 16.5kV 1 1 3 1.040 0.0 0.0 0.0 0.0 0.0 16.5 1.040 0.0 0.0 0.0 0.0 0 2 Bus2 18kV 1 1 2 1.025 0.0 0.0 0.0 163.0 0.0 18.0 1.025 99.0 -99.0 0.0 0.0 0 3 Bus3 13.8kV 1 1 2 1.025 0.0 0.0 0.0 85.0 0.0 13.8 1.025 99.0 -99.0 0.0 0.0 0 4 Bus4 230kV 1 1 0 1.000 0.0 0.0 0.0 0.0 0.0 230.0 0.000 0.0 0.0 0.0 0.0 0 5 Bus5 230kV 1 1 0 1.000 0.0 125.0 50.0 0.0 0.0 230.0 0.000 0.0 0.0 0.0 0.0 0 6 Bus6 230kV 1 1 0 1.000 0.0 90.0 30.0 0.0 0.0 230.0 0.000 0.0 0.0 0.0 0.0 0 7 Bus7 230kV 1 1 0 1.000 0.0 0.0 0.0 0.0 0.0 230.0 0.000 0.0 0.0 0.0 0.0 0 8 Bus8 230kV 1 1 0 1.000 0.0 100.0 35.0 0.0 0.0 230.0 0.000 0.0 0.0 0.0 0.0 0 9 Bus9 230kV 1 1 0 1.000 0.0 0.0 0.0 0.0 0.0 230.0 0.000 0.0 0.0 0.0 0.0 0 -999 BRANCH DATA FOLLOWS 9 ITEMS 1 4 1 1 1 0 0.0000 0.0576 0.0000 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2 7 1 1 1 0 0.0000 0.0625 0.0000 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3 9 1 1 1 0 0.0000 0.0586 0.0000 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 4 5 1 1 1 0 0.0100 0.0850 0.1760 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 4 6 1 1 1 0 0.0170 0.0920 0.1580 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 5 7 1 1 1 0 0.0320 0.1610 0.3060 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6 9 1 1 1 0 0.0390 0.1700 0.3580 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 7 8 1 1 1 0 0.0085 0.0720 0.1490 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 8 9 1 1 1 0 0.0119 0.1008 0.2090 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 -999 LOSS ZONES FOLLOWS 1 ITEMS 1 IEEE 30 BUS -99 INTERCHANGE DATA FOLLOWS 1 ITEMS -9 1 2 Frank 230 0.0 999.99 Anderson9 Anderson 9 Bus Test Case TIE LINES FOLLOWS 0 ITEMS -999 END OF DATA